Four-electrode soil resistivity measurements do not use the permanent rods of the installation. Removable test rods or stakes are used instead: they are driven in along a line, measured and pulled out. They are the contact points between the instrument and the ground.
What function they serve
Two of the rods inject the test current into the soil; the other two are used to measure the potential difference. Their requirements are different: the current rods need good contact so that the current the instrument requires can flow, while for the potential rods contact matters less because almost no current flows through them, as long as it is not excessive.
Desirable characteristics
- A material resistant to corrosion and to deformation when driven, such as stainless steel.
- A penetrating tip and an end with a terminal for connecting the test lead.
- Enough length to drive in only a small depth, meeting the condition that the electrode be much shallower than the spacing between electrodes.
- A clean surface, to ensure electrical contact at the lead.
How to use them properly
They are placed in line, at equal spacings measured with a tape; they are driven to a uniform, small depth; and contact with the soil is checked, wetting the ground if it is very dry. If a rod ends up on a stone or on loose gravel, the reading can be noisy or unstable. Keeping the test leads apart from each other reduces coupling.
What errors misuse causes
- A driving depth that increases with the spacing, which distorts the calculated value.
- Unequal spacings, which invalidate the array formula.
- Placing them near pipes or metal fences.
At sites with nearby buried or energized installations, the measurement must be made by qualified personnel.