Concept
An MCC is a modular assembly in which each motor has its own functional unit. That unit contains the disconnecting means and short-circuit protection, the contactor or starter, the overload protection and, if needed, the control or the drive. All units are fed from the same horizontal bus running along the length of the assembly.
How it is built
- Vertical sections: enclosure columns joined to each other.
- Main horizontal bus: receives the supply and distributes it to each section.
- Vertical buses: in each section, they take power from the horizontal bus and deliver it to the units through connectors.
- Units: many are withdrawable or plug-in, so they can be removed from the enclosure without dismantling the assembly.
- Wireways: separate the power and control conductors of each unit.
What it offers over an ordinary panel
Standardization makes the units interchangeable and maintenance faster and more orderly. All motor control is concentrated in one place, which makes operation and diagnosis easier. There are different degrees of separation between units and buses, and variants designed to contain an internal arc and protect the operator. Many MCCs incorporate digital communication, so that starters and drives report status, current, and faults to a control system.
What to watch
- Heating of buses and connections, which is checked with thermography.
- The ability to withstand the available short-circuit current.
- The effect of drives on the MCC: heat, harmonics, and compatibility with other starters.
- The condition of the connectors on withdrawable units, which wear with operation.
When it does not apply
For a few motors or small installations, a conventional panel with individual starters may be sufficient. An MCC justifies its construction when there are many motors, ease of maintenance is required, or process continuity is wanted. Work on an MCC that is energized or has live buses, even when withdrawing units, requires qualified personnel and procedures in accordance with the applicable regulations.