What is a counterpoise in a grounding system?

It is a buried horizontal conductor, normally radial or parallel to a line, that is added to the electrode to disperse current when deep electrodes cannot be driven or when the impedance to lightning discharges must be reduced.

Definition

A counterpoise, also called a ground counterpoise, is a bare conductor laid horizontally underground at a moderate depth and connected to the base of a tower or structure. It is the most widely used form of horizontal electrode when the ground is rocky or shallow, so that a vertical rod cannot be driven.

Configurations

  • Radial. One or more conductors fan out from the base of the structure.
  • Parallel to the line. A continuous conductor is laid along the route, connecting several structures.
  • Ring. It surrounds the base of the structure.

Why it is used

A transmission tower must dissipate the current of a lightning stroke that hits the structure or the shield wire. If the resistance to ground is high, the tower potential rises and a backflash (back flashover) can occur across the insulation. The counterpoise lowers the tower resistance by distributing the current along a length of conductor.

The important detail: it is not a lumped resistance

With lightning, which has a very fast front, the current entering the counterpoise travels along the conductor as it would on a transmission line with losses to the soil. A part of the conductor far from the injection point contributes little, because the wave is attenuated before reaching it. There is therefore an effective length beyond which extending the counterpoise does not improve lightning performance, although it may improve the low-frequency resistance. The effective length depends on the soil resistivity and on how fast the wave front is.

What is seen in the field

The tower footing resistance measured at low frequency may be acceptable and the line may still suffer lightning outages if the impulse impedance is high. When measuring, it is advisable to distinguish between the two. It is also necessary to check that the conductor has not been cut by agricultural or civil works, and that the connections have not corroded.