What is a Class A power quality analyzer?

A Class A power quality analyzer is an instrument that meets the strictest method and uncertainty requirements of IEC 61000-4-30, so that two Class A instruments measuring the same signal give comparable results.

What the class means

IEC 61000-4-30 defines how to measure each power quality parameter and sets performance classes. Class A is the most demanding: it specifies the measurement algorithm, the aggregation windows, the uncertainty requirements, time synchronization and how data are handled during events. Less demanding classes, such as S or B, allow more freedom in the methods and greater uncertainty.

What changes in practice

  • Comparability: two Class A instruments measuring the same signal give results within the stated uncertainty. This is not guaranteed between a Class A instrument and one with no defined class.
  • Defined method: the calculation of the RMS value per window, sag detection and the calculation of harmonics and unbalance follow fixed procedures.
  • Standardized aggregation: intervals are aligned to the clock, and gaps between intervals are avoided.
  • Time synchronization: the time is kept against an external reference within a tolerance, which makes it possible to correlate events at different points.
  • Data flagging: when a sag or interruption occurs, the values for that interval are flagged so they do not contaminate the statistics.

When it is needed

When the result will be used to verify compliance, resolve a dispute between parties or compare measurements from different points and dates, a Class A instrument with current calibration and traceability is advisable. For internal diagnostics, where the aim is to find the cause of a fault, an instrument of another class may be enough, provided its limitations are known.

When it does not apply

The instrument class alone does not guarantee a good measurement: the result also depends on the current sensors, the transformation ratios, the connection and the configuration. A poorly connected Class A instrument gives poor results. Moreover, the class is defined for the voltage signal; performance with certain current sensors must be checked separately in the data sheet.

Connection to energized installations must be done by qualified personnel.