What does the IEC 62109 standard cover for inverters?

The IEC 62109 standard deals with the safety of power converters for photovoltaic systems, including inverters: it requires them to protect against electric shock, hazardous energy, fire and failures, and to detect and handle ground faults.

General scope

The standard is divided into a part with general requirements and another specific to inverters. It focuses on equipment safety, not on efficiency or on performance with respect to the grid. For the inverter, this includes what happens in the event of a failure of the equipment or of the connected array, which is highly relevant because the DC side stays at voltage as long as there is light.

Topics it addresses

  • Protection against electric shock: insulation, grounding of accessible parts and limitation of accessible voltages.
  • Protection against fire and component overheating.
  • Detection of array ground faults, in order to raise an alert or disconnect.
  • Measurement of the array insulation resistance before connecting, and monitoring of residual currents during operation.
  • Marking and documentation, with warnings for those who install and repair the equipment.

Why ground fault detection matters

A floating photovoltaic array can have a first ground fault with no visible consequences, but that first fault removes the protection against the second, which can create fault currents circulating through the wiring. Inverters include monitoring to detect the first fault and react. When the inverter locks out on a low insulation warning, the cause is usually in the array, not in the equipment.

How compliance is interpreted

Conformity indicates that the model has passed safety tests, not that it meets grid connection requirements, which are verified against other standards and local regulations. In a technical review, the certificate is checked against the model and version installed.

Notice

This guide describes only the general scope of the standard. The requirements, the tests and their order change between editions, so consult the current edition and the one required by the contract or the authority. Any work on an energized photovoltaic array, with DC voltages that are not interrupted by opening a disconnect switch on the AC side, must be carried out by qualified personnel in accordance with the applicable electrical safety regulations.