24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

What the IEC 60751 standard specifies for platinum sensors

The IEC 60751 standard covers industrial platinum resistance thermometers: it defines the resistance-temperature relationship, the tolerance classes and the general requirements for the sensor.

General scope

IEC 60751 deals with industrial platinum resistance sensors, known as Pt100, Pt1000 and variants. Its practical value is that it sets a single relationship between resistance and temperature, so that a sensor from any manufacturer that complies with the standard is interchangeable with another within its tolerance.

What it defines

  • The resistance-temperature relationship: a polynomial equation, derived from the Callendar-Van Dusen form, with coefficients established for industrial-purity platinum.
  • The nominal value: the resistance at zero degrees Celsius, which gives the type its name (Pt100 means one hundred ohms at that temperature).
  • The temperature coefficient associated with that platinum purity.
  • The tolerance classes: permitted deviation limits from the nominal curve, which grow with distance from zero degrees and vary between classes.
  • General requirements: such as insulation, stability and measurement techniques, which depend on the edition in force.

What the standard does not do

It does not guarantee the accuracy of a specific sensor once installed. The tolerance describes how far a new sensor can depart from the nominal curve, but drift, self-heating, lead resistance and mounting all affect the final result. Nor does it replace calibration: a sensor within its class can still have an error that matters in a demanding process.

What the engineer sees

In the field, the standard shows up on the data sheet: type (thin-film or wire-wound), class, wire configuration and operating range. If the sensor is calibrated, the results can be expressed as a deviation from the standardized curve or fitted to its own coefficients, which reduces the error of the combined sensor and meter.

How to use it

Before specifying or comparing sensors, consult the edition of the standard in force and verify the limits and classes applicable at the project date. The class chosen must correspond to the process requirement, and the instrument reading the sensor must use the same curve to avoid introducing a systematic error.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer