What does the IEEE 1584 guide calculate?

The IEEE 1584 guide provides calculation models for estimating arcing current, incident energy and the arc flash boundary from system data, equipment configuration and the protection's clearing time.

What it is

IEEE 1584 is a technical guide from the Institute of Electrical and Electronics Engineers for performing arc flash hazard calculations. It offers empirical models, developed from testing, to predict what would happen during an arc event in electrical distribution equipment.

What results it gives

  • Arcing current: the current that actually flows through the arc, which is different from, and normally lower than, the bolted fault current because the arc has its own impedance.
  • Incident energy: the thermal energy per unit area that would reach a surface located at a given working distance.
  • Arc flash boundary: the distance beyond which the incident energy drops to a level at which an unprotected person could suffer a curable burn.

Variables involved

  1. System voltage and available fault current.
  2. Arc clearing time, which depends on the protection.
  3. Electrode configuration: vertical, horizontal, with or without a barrier, in a box or in open air.
  4. Dimensions of the box or enclosure.
  5. Working distance between the potential arc and the body.
  6. Conductor gap and system grounding condition.

How its results are interpreted

Time is the variable with the greatest practical effect: energy grows with duration, so reducing the trip time reduces the hazard. It is also important to evaluate the lowest arcing current case, because a lower current can make the protection take longer and the resulting energy higher.

Limits

  • It is a model with ranges of validity for voltage, current, distances and configurations; outside them, the calculation loses reliability.
  • It depends on actual installation data and on protection settings not having changed.
  • It estimates energies with uncertainty; it does not predict a particular event exactly.
  • It does not replace the task risk analysis or the selection of protective equipment.

Note on editions

The guide has been revised and its models have changed between editions, so the current edition must be consulted. Studies and work involving arc risk must be done by qualified personnel, following the applicable regulations.