Definition
THD stands for total harmonic distortion. It is calculated as the square root of the sum of the squares of the RMS values of all the harmonics, divided by the RMS value of the fundamental component, and is usually expressed as a percentage. A pure sine wave has zero distortion.
Why distortion occurs
Nonlinear loads, such as rectifiers, drives, and switched-mode power supplies, do not draw a sinusoidal current even when the voltage is sinusoidal. According to Fourier’s theorem, any periodic waveform is equivalent to a sum of sine waves whose frequencies are multiples of the fundamental. Those multiples are the harmonics.
Voltage THD and current THD
These are different quantities. Current distortion is determined by the load. Voltage distortion results from that current flowing through the source impedance, so it depends on how “strong” the grid is at that point. A load with high current distortion can produce little voltage distortion if the grid is strong, and vice versa.
How to interpret a value
- A high current THD at very low load may not be relevant, because the absolute current is small. That is why some standards evaluate current distortion relative to the maximum demand current and not the instantaneous current.
- THD alone does not tell you which harmonics are present. A fifth harmonic and a third harmonic have different effects on motors, neutrals, and capacitors.
- Some instruments calculate THD relative to the fundamental and others relative to the total RMS value. You need to know which one the instrument uses before comparing with a criterion.
Practical effects
Harmonics increase the RMS value of the current and with it losses and heating, and they can cause resonances with capacitors, erratic protection trips, and errors in average-responding meters. Voltage THD is the indicator most often used to find out whether other grid users are affected.
When it is not enough
Diagnosis requires the spectrum by harmonic order and the waveform. THD serves as a summary and for comparison with the limits of the applicable standard in its current edition.