Definition
The point of common coupling is the point on the electrical grid, normally on the supply side, from which other loads can be fed in addition to the one being analyzed. It is the practical boundary between what belongs to one user and what is shared with others. The abbreviation PCC is in common use.
Why it matters
A disturbing load, such as a large drive or an arc furnace, distorts the voltage at its own connection point. That distortion propagates through the shared impedance and reaches the other users connected to the same point. What affects a third party is what happens at the point where that party is also connected. That is why limits on harmonic distortion, flicker, and unbalance are set for the PCC and not for the terminals of each piece of equipment.
How it is identified
- In an industrial installation fed by its own transformer, it is usually the point of interconnection with the utility, although the exact definition is set by the standard or the contract.
- In a building with a service entrance shared by several tenants, it may be at the common bus before the branch to each tenant.
- It does not necessarily coincide with the location of the billing meter.
What it means for measurement
If measurements are taken at a point other than the PCC, the values cannot be compared with the limits. Measuring at an internal panel may show more distortion than the third party sees, because the impedance up to that panel is higher. Measuring on the supply side shows the shared effect. To diagnose an internal problem, it is best to measure where the load or the affected equipment is; to demonstrate compliance, at the PCC. Both measurements are often made.
Example of the reasoning
If a large drive raises the voltage distortion on the plant’s transformer bus and that transformer also feeds another user, the transformer bus is a candidate PCC. Its formal identification is made with the applicable standard or with the utility. Medium-voltage measurements must be made by qualified personnel.