What Does “Libranza” Mean?

In the electrical field, a libranza is the formal authorization to work on equipment or a circuit that has been disconnected, isolated, verified de-energized and grounded, under the responsibility of identified persons.

What it is

The libranza is both a permit and a procedure. It ensures that the person who will do the work and the person who operates the installation share the same knowledge of which equipment is out of service, who handed it over, who received it and under what conditions. The term is used in the Mexican electrical sector, and the exact procedure depends on the company and the applicable regulations.

Why it is done

Most serious accidents in electrical work occur when someone believes a circuit is de-energized and it is not, or when someone else energizes it during the work. The libranza puts each step in writing and assigns responsible persons, so that accidental energization is unlikely.

General sequence

  1. Request: the work, the equipment and the limits of the intervention are described.
  2. Isolation: the disconnection points that feed the equipment are opened, including secondary sources, backfeeds and control supplies.
  3. Lockout and tagout: each open point is secured with a lock and tag so that it cannot be closed.
  4. Verification of absence of voltage with a suitable instrument, proven before and after the measurement.
  5. Temporary grounding where applicable, for protection against energization or induced voltage.
  6. Handover: the person operating the installation hands over in writing to the person responsible for the work.
  7. Return: once the work is finished, personnel are withdrawn, grounds and tools are removed, the lockouts are canceled and the equipment is returned to operation.

Relationship with other concepts

Lockout and tagout is part of the libranza but does not replace it: the libranza also includes coordination and responsibility between those who operate and those who work. Absence of voltage is always verified, even with the breaker open.

Common mistakes

  • Relying on the position of a breaker without verifying the absence of voltage.
  • Forgetting alternate sources, such as backfeeds, generators or control voltages.
  • Carrying out the work under a libranza for other equipment or a different scope.
  • Removing other people’s locks or returning the equipment before all personnel have left.

All work must be performed by qualified personnel, following the applicable safety regulations and the facility’s procedures.