What does effective value or true RMS mean?

The true effective value, or true RMS, is the value of a signal that produces the same heating in a resistor as a direct current of that value, calculated from the actual waveform.

Definition

RMS stands for “root mean square.” The signal is squared at each instant, averaged over a period, and the square root is taken. The result is the DC current or voltage value that dissipates the same power in a resistor. That is why the RMS value is the one directly related to heating and power.

For a pure sine wave, the RMS value is the peak value divided by the square root of two. That relationship holds only for sine waves.

What a true RMS instrument does

It calculates the square, the average, and the root on the waveform it actually receives, either with an analog circuit or by sampling and computing digitally. An average-responding instrument measures the average rectified value and multiplies it by a factor that assumes a sine wave. With a sine wave, both agree. With a distorted waveform, such as the current of a switched-mode power supply or a drive, the averaging instrument gives an incorrect reading.

What is seen in practice

  • The current of a rectifier with a capacitive filter arrives in narrow pulses. Its peak value is high relative to the RMS value; in other words, it has a high crest factor.
  • A clamp meter without true RMS can indicate less than the real current in the neutral of a system with electronic loads, and the conductor can get hotter than the reading would suggest.
  • Two instruments will read the same on a resistive load and differently on an electronic load.

Limits of true RMS

It is not enough for the instrument to claim true RMS. Its bandwidth matters, because high-order harmonics are left out if it is insufficient, and so does its crest factor capability, because a peak above what the range accepts saturates the circuit and distorts the measurement. The calculation window also makes a difference: one-cycle and multi-second readings can differ on fluctuating loads.

Common mistakes

  • Using an averaging instrument to check currents in circuits with nonlinear loads.
  • Applying the sine wave relationship to convert peak to RMS on a waveform that is not a sine wave.
  • Comparing readings without checking the bandwidth and window of each instrument.