First, what demand is
Electrical demand is the average power an installation draws during a fixed measurement interval. The meter calculates that average in each successive time window and retains the highest value of the billing period, which is the maximum measured demand. An average per window is used, rather than the instantaneous peak, because supply infrastructure is sized for loads sustained over time, not for peaks lasting a few cycles.
What makes it “billing” demand
Billing demand is the value that results from applying the rules of the contracted rate to the measurements. Depending on the rate, it may depend on the maximum demand of the period, on demands in different time blocks, on weighting factors, or on the contracted demand. That is why it can differ from the maximum measured demand. The exact definition is in the rate provisions in force and in the contract, and must be consulted there.
What the engineer sees in practice
- A very brief motor start has almost no influence on the window average, whereas a high load sustained for the whole interval does.
- Two loads that coincide in time increase demand more than if they are staggered, even though the total energy consumed is the same.
- Power factor also plays a part in billing under many rates, so improving it can reduce the charge even if demand does not change.
How it is managed
- Record the demand profile by interval to see when the maximum occurs.
- Identify which loads coincide at that moment.
- Stagger starts and processes, or use demand control that disconnects deferrable loads.
- Check the results against the next period’s billing.
When the reading is misleading
Comparing an analyzer reading with the bill requires that the integration interval and window alignment match those of the utility’s meter. If they do not match, the maximum values may differ.