What it is about
ASTM F1506 is a specification from ASTM International for textile materials intended for the clothing of electrical workers exposed to a momentary electric arc and related thermal hazards. It defines which properties a fabric must demonstrate to be considered suitable for this use.
What is evaluated
- Flame resistance: the material must not sustain combustion once the source is removed, and must not melt or drip.
- Arc rating: a measure of thermal protection against an arc, obtained by exposing the fabric to laboratory arcs and recording the transmitted heat with sensors.
- Additional fabric requirements, such as dimensional stability and mechanical strength, according to the applicable edition.
How the arc rating is expressed
It is reported as a value of energy per unit area. Depending on how the material behaves, the rating is expressed in one of two ways:
- ATPV (arc thermal performance value): the incident energy at which there is a fifty percent probability that the transmitted heat will cause a second-degree burn.
- EBT (energy breakopen threshold): the energy at which the material breaks open, forming a hole, before the burn criterion is reached.
The arc value marked on the garment is the lower of the two, so it is interpreted conservatively.
How the result is used
The fabric’s rating is compared with the incident energy calculated for the task, and the garment or ensemble must equal or exceed that energy. Protective equipment is marked with its rating so the user can check this.
What it does not cover
- It does not define the selection procedure for a particular installation.
- The test is carried out under laboratory conditions; a real event may differ.
- It does not guarantee that there will be no injury; it only seeks to limit the severity of burns.
- It does not, on its own, include the performance of the complete garment, such as closures, threads or labels, which have their own requirements.
Consult the current edition of the specification. Work involving arc risk must be done by qualified personnel, following the applicable regulations.