24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

What Does “Ampacity” Mean?

Ampacity is the maximum current a conductor can carry continuously, under the given installation conditions, without its insulation exceeding its permitted temperature.

Definition

Ampacity is the term that sums up a conductor’s current-carrying capacity. It is the current that, flowing continuously, leaves the conductor in thermal equilibrium below the maximum temperature its insulation can withstand. It is not a fixed property of the conductor: it depends on how and where it is installed.

What determines it

The conductor generates heat through the Joule effect, proportional to its resistance and to the square of the current, and dissipates it to the surroundings. Ampacity is the current at which the two balance at the limit temperature. From this follow the factors that modify it:

  • Material and cross section: a larger cross section and better conductivity reduce resistance and the heat generated.
  • Maximum insulation temperature: insulation that tolerates a higher temperature allows more current.
  • Ambient temperature: the higher the ambient temperature, the less margin there is for dissipation.
  • Grouping: several current-carrying conductors in the same raceway heat one another and require downward correction.
  • Installation method: in free air, in cable tray, in conduit, direct-buried or in duct, the dissipation changes.
  • Terminals: the equipment it connects to also has a temperature limit, which may be more restrictive than that of the cable.

What ampacity is not

It is not the ability to withstand a short circuit, which depends on the brief energy and the material and is verified separately. Nor is it the breaker rating: the protective device must protect the conductor, so its settings are related to ampacity, but they are not the same thing. And it is not voltage drop, which may be the criterion that determines the cross section in long circuits.

How it is used in practice

  1. Calculate the load current, with the applicable continuous-duty factor.
  2. Take the conductor’s base ampacity under the reference conditions set by the regulations.
  3. Apply correction factors for temperature and grouping.
  4. Check against the terminal limit and the protection.
  5. Review voltage drop and short-circuit withstand.

The numerical values are found in the tables of the applicable current regulations; they should not be used from memory. With harmonic loads, the neutral can run hotter than expected and must be reviewed.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer