What it is and how it starts
It is a structure of fine, branching channels inside solid insulation, resembling the branches of a tree, that grows through the action of electrical discharges. To start, it needs a point where the local electric field is much higher than the average.
Initiation points
- Protrusions on the semiconducting shield that dig into the insulation.
- Impurities or conductive particles embedded in the material.
- Voids or cavities from manufacturing or from joints.
- Areas mechanically damaged during installation.
- Water trees that, as they develop, promote the initiation of an electrical tree.
How it progresses
Partial discharges occur at the point of concentration. Each discharge chemically degrades and erodes the polymer slightly, creating a channel. The channel branches and advances toward the other electrode. Growth can be slow for years and then accelerate as it nears the other side, until a channel reaches the opposite electrode and a complete breakdown occurs.
What factors accelerate failure
- High electrical stress, especially at sharp defects.
- Transient overvoltages from switching or lightning, which can initiate or activate a latent tree.
- Temperature and thermal cycling, which strain the material and the interfaces.
- Moisture, which facilitates the conversion of water trees into electrical trees.
What is seen in practice
Before failure, the cable may show measurable partial discharges and an increased dissipation factor. After failure, examination of the insulation reveals the branching channel that led back to the origin. Failure often occurs during an overvoltage, so the external event is mistaken for the cause; the underlying cause is the pre-existing defect.
These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.