When a fault injects current into the soil, the surface potential is not uniform: it is highest near the injection point and decreases with distance. That distribution is the cause of two different hazards for people.
Step voltage
This is the potential difference between two points on the surface separated by the distance of one step. A person standing with feet apart is subjected to that difference, and current flows from one foot to the other through the legs. It is dangerous above all when walking near an electrode or a structure through which fault current is flowing.
Touch voltage
This is the difference between the potential of a grounded metal structure and that of the surface on which the feet rest, when a person touches that structure. The current path passes through the hand, the trunk and the feet, which makes it more severe for the heart than step voltage, and that is why touch voltage is usually the governing design criterion.
What defines the tolerable limit
- The duration of the fault: the faster the protection acts, the more the body can tolerate.
- The resistance of the body and of the contact with the ground.
- The resistivity of the surface layer: a layer of gravel improves the insulation between the foot and the soil.
What the design does
A grounding system in the form of a grid reduces these voltages by distributing the current and smoothing the gradients. The maximum expected values are calculated and compared with the tolerable limits of the current standard. If they do not comply, conductors are added, spacing is reduced, the surface layer is improved or clearing times are shortened.
What to check first
An installation with low ground resistance does not guarantee safe touch voltages. Check the continuity to the structures that people can touch and the surface layer in access areas.
Measurements and inspections in energized installations must be performed only by qualified personnel, in line with the applicable safety regulations.