The essentials: each has its own reference
Pressure is force per unit area, but a pressure figure only makes sense if you know what it is measured against. Hence the three types.
Absolute pressure
It is measured relative to total vacuum, which is the physical zero of pressure. It cannot be negative. It is the pressure that enters into the gas laws and thermodynamic properties, such as the boiling point of a liquid.
Gauge pressure
It is measured relative to the local atmospheric pressure. It is what an ordinary pressure gauge shows with its connection open to the air: zero when the system is open to the atmosphere. It can be negative if the system is below atmospheric pressure; this is then called partial vacuum.
Differential pressure
It is the difference between two pressures, one connected to each port of the sensor. The absolute level of the two does not matter, only their difference. It is used to measure the drop across filters, flow with an orifice plate or level in closed tanks.
How they relate
Absolute pressure is the sum of gauge pressure and atmospheric pressure. Atmospheric pressure is not constant: it varies with altitude and weather. Therefore, the same absolute pressure translates into different gauge readings in different places or on different days.
| Type | Reference | Typical use |
|---|---|---|
| Absolute | Perfect vacuum | Vacuum, barometry, gas processes |
| Gauge | Local atmosphere | Lines, tanks, pneumatics, hydraulics |
| Differential | Another process pressure | Filters, flow, level |
What the engineer sees
A gauge sensor vented to the atmosphere follows weather variations, which at low ranges can appear as zero drift. An absolute sensor shows a nonzero value at atmosphere, which is to be expected: it is indicating atmospheric pressure. Confusing the types when specifying or calibrating produces errors equal in magnitude to atmospheric pressure.
How to interpret the result
Before reading or comparing any figure, ask: gauge, absolute or differential? And, if differential, what is the line pressure common to both ports?