IEC 60909 describes a method for calculating short-circuit currents in three-phase AC networks based on an equivalent voltage source at the fault location, with no need for a prior load flow study.

The idea behind the method

The standard replaces the entire network, at the moment of the fault, with a single equivalent voltage source applied at the short-circuit location. All other voltage sources are set to zero and the network elements are represented by their impedances. The result is a linear, reproducible calculation that does not require knowledge of prior load conditions.

What simplifications it adopts

  • Passive loads and line capacitances are neglected, except in the zero-sequence components where appropriate.
  • The equivalent voltage is obtained from the nominal voltage multiplied by a voltage factor, which covers network voltage variations and takes a different value for calculating the maximum case and the minimum case.
  • The impedances of generators, transformers and power station units are corrected with defined factors to reflect actual operating conditions.
  • Motors and other rotating machines are treated as sources that contribute fault current.

What quantities it calculates

The standard defines several currents used for different purposes:

  • The initial symmetrical short-circuit current, the starting point of the calculation.
  • The peak current, relevant to electrodynamic stresses and making capacity.
  • The symmetrical breaking current, which is compared with the breaking capacity of circuit breakers.
  • The steady-state current, associated with thermal effects.

Maximums and minimums

The maximum case is used to verify equipment ratings; the minimum case, to check that the protection detects low-current faults. A frequent mistake in studies is to calculate only the maximum and assume that the protection will see the minimum fault.

How the results are interpreted

The currents are compared with the interrupting and withstand ratings of circuit breakers, busbars and cables. If the calculated value exceeds the rating, the equipment must be changed, the fault limited or the network reconfigured. Because the method is a standardized convention, it differs from other procedures that model load conditions, and the results may not match exactly. To apply it, the current edition of the standard must be consulted.