The source: fast switching
A variable-frequency drive produces its output voltage by pulse-width modulation: transistors that switch between two voltage levels many times per second. Each transition has a very high rate of voltage change over time. The spectral energy of these pulses extends to frequencies much higher than the switching frequency and reaches the radio band.
How the disturbance gets out
- The capacitance between the motor windings, the cable and ground converts the fast voltage change into common-mode current that returns through ground or through the chassis.
- The motor cable, long and carrying high-frequency pulses, acts as an antenna and radiates.
- The common-mode current also reaches the power supply network and other equipment connected to the same grounding system.
Coupling paths into the communications equipment
| Path | How it happens |
|---|---|
| Conducted | They share a power supply or ground, and the noise enters through those cables |
| Capacitive/inductive coupling | Communication cables run parallel to the motor cable |
| Radiated | The antenna or cable of the equipment picks up the field from the motor cable |
| Common ground impedance | The drive current creates a drop in the ground that the other equipment takes as a signal |
Mitigation, in order of effectiveness
- Shielded motor cable with a 360-degree shield termination at both ends.
- A filter at the drive input, suitable for common mode, and common-mode chokes at the output.
- Output filters that reduce the rate of voltage change.
- Separation between the power cable and the communication cables, with perpendicular crossings where crossing is unavoidable.
- A consistent, low-impedance ground connection between drive, motor and enclosure.
- On the communications equipment: shielded cables and filtering of its power supply.
Drives operate at hazardous voltages and hold a charge on their DC bus after being switched off. Any intervention must be carried out by qualified personnel, in accordance with the applicable regulations.