What changes between the two options
With the cover open, the camera sees the connections directly and the measurement depends only on emissivity, distance, and surroundings. With an infrared window, a window is fitted in the door, made of a material that is transparent to infrared radiation, unlike ordinary glass, which blocks it. The camera looks through it with the cover closed.
Advantages and limits
| Aspect | Open cover | Infrared window |
|---|---|---|
| Personnel exposure | Higher, energized equipment accessible | Lower, equipment remains closed |
| Accuracy | Highest possible | Reduced by transmission below one |
| Coverage | Everything visible on opening | Only the field behind the window |
| Airflow | Opening alters the thermal balance | Normal operating conditions |
Attenuation in the window
No window transmits everything. The material’s transmission is below one, so the camera receives less radiation than leaves the object and reads a lower temperature. Many cameras allow a transmission value to be entered to compensate, and the window manufacturer specifies it for its material. If it is not compensated, the hot spot appears less serious than it is.
How to decide
- If the equipment cannot be opened safely during operation, the window is the practical option.
- If the point to be checked is not within the window’s field, there is no way to see it without opening.
- One risk of the open cover is that opening changes the cooling conditions and can mask an anomaly.
Safety
Opening covers on energized equipment is an operation with electrical risk, including arc flash. It must be performed only by qualified personnel, with the protective equipment and procedures required by applicable regulations. Windows reduce exposure, but they do not replace those requirements.