Three criteria, the most demanding governs
There is no “correct” size based on a single criterion. The minimum is calculated for each one and the largest of the results is chosen.
1. Ampacity
Ampacity is the current a conductor can carry continuously without its insulation exceeding its maximum temperature. It depends on factors that the table value alone does not include: ambient temperature, the number of conductors grouped in the same raceway, the installation method (air, duct, cable tray, buried), and the temperature that the terminals where it connects can withstand. When several cables share a raceway they heat one another, so their individual capacity is reduced. The design current usually also includes a margin for continuous loads and is coordinated with the rating of the overload protection, which must protect the conductor.
2. Voltage drop
A long conductor can meet the ampacity requirement and still deliver too low a voltage at the load. The drop is calculated using the conductor’s resistance and reactance and the current, both in operation and, for motors, during starting. If the result exceeds the limit set by the applicable regulations, the cross-section is increased.
3. Short-circuit withstand
During a fault, the current heats the conductor with almost no heat dissipated to the surroundings. Under this adiabatic assumption, the allowable thermal energy is proportional to the square of the cross-section. The relationship is expressed as I²·t = k²·S², where I is the fault current, t the time the protection takes to clear it, S the cross-section, and k a constant that depends on the conductor and insulation material. Solving for it, the minimum cross-section is S = I·√t / k. This links conductor size to the speed of the protection: a slower device requires a larger cross-section, and a current-limiting one reduces it.
What else comes into play
- The ground fault current value, so that the protection trips within the required time.
- Harmonics and a loaded neutral, which can reduce usable capacity.
- The type of material, copper or aluminum, which changes the resistance and the constant k.
Which criterion usually decides
In short, heavily loaded circuits, ampacity usually governs. In long feeders, voltage drop. In taps close to large transformers with slow protection, short-circuit withstand. Table values and limits must be taken from the current edition of the applicable standard. Installation must be carried out by qualified personnel.