Why charge remains
Insulation with conductors on both sides behaves like a capacitor. During the test it stores energy, and the dielectric absorption phenomenon also causes part of the charge to be released slowly. A long cable, a generator or a large transformer can retain a dangerous charge for a long time after the test source is removed.
What happens if it is skipped
Touching or disconnecting the equipment without discharging it can give a person an electric shock. In addition, if it is reconnected to the circuit with residual charge, the voltage can damage connected equipment. Most deceptive of all, after discharging and removing the ground, voltage can reappear at the terminals because of dielectric absorption.
How it is done in practice
- Reduce the source voltage to zero and wait for the instrument itself to discharge the equipment, if it does so through an internal resistor.
- Do not rely on the instrument alone. Verify the discharge with an independent method suited to the voltage.
- Discharge with an insulated stick fitted with a discharge resistor, so that the energy dissipates in a controlled way and not through a sudden short circuit. Connect the ground end first and then the conductor.
- Solidly ground the conductors and keep the ground in place long enough; on equipment with high capacitance or absorption, the time is comparable to or longer than the time the voltage was applied.
- Remove the ground only at the end, when the work is finished and the equipment is about to be reconnected.
What to check first
Before approaching, confirm that the test source is at zero and disconnected, that a reliable path to ground exists, and that the discharge accessories are in good condition and rated for the voltage tested.
The procedure is the responsibility of qualified personnel, who must follow the facility’s regulations and procedures; an insufficient discharge can be fatal.