What a transferred voltage is
When a fault injects current into a substation’s ground grid, the potential of that grid rises relative to remote earth. This is called ground potential rise. If a metallic conductor leaves the zone, such as a pipe, a cable shield, a fence, a rail or the neutral of a line, it carries that potential to a point where the soil is at a different level. A person touching that conductor outside is subjected to the difference. It also happens the other way around: a conductor from a remote point can bring its potential into the substation.
Protection strategies
- Equipotential bonding. Bond together everything a person can touch at the same time so that there is no dangerous difference between its parts.
- Insulation of outgoing conductors. Insulating joints in pipes and insulating sections in rails, so that the conductor does not carry the potential outward.
- Separation of grounds. Perimeter fences are connected to or separated from the grid according to the design, to control touch voltages at the edge.
- Communications. Telecommunication circuits leaving the substation use isolation, isolation transformers or optical fiber, so as not to transfer potential over the copper.
- High-resistivity surface. A layer of gravel or another material on the surface increases the resistance between the foot and the soil and reduces the current through the body.
- Reducing the potential rise. Improve the ground grid or divert part of the current through other paths, such as shield wires and cable neutrals.
How it is analyzed
The fault current that actually enters the soil, the resulting potential rise and the tolerable step and touch voltages are calculated. Then all the conductors crossing the boundary of the installation are identified, and how each one is controlled is decided. Field measurements verify that the bonds and insulation work as designed.
This is high-voltage work: design, verification and switching operations are the responsibility of qualified personnel in accordance with the applicable regulations.