Why preparation determines quality
A heating fault shows up only when current is flowing. Arriving without a plan means measuring at low load, not seeing the component or wasting time under conditions that invalidate the reading.
Before going to the site
- Scope: which panels, control centers and equipment are included, and what criteria will be used to classify the findings.
- Available information: single-line diagrams, equipment identification and previous inspections for comparison.
- Load: schedule the inspection at a time when circuits operate under significant, stable load; at low load, incipient faults are not visible.
- Permits and coordination: with the person responsible for operations, for opening doors and for any switching.
- Equipment: camera charged and with its verification up to date, clean lens, current meter to note the load, and recording form.
On site
- Check the ambient conditions: air currents, direct sun, reflective surfaces and heat sources that affect the image.
- Define emissivity, reflected apparent temperature and distance settings according to the materials.
- Identify each piece of equipment and record the load at the time of the shot.
- Go through the three phases, joints and protective devices in a fixed order so that none is missed.
- Take thermal and visible images from the same angle to make reporting easier.
What an engineer sees in practice
The biggest constraint is usually access. Components behind fixed covers cannot be seen without removing the guard or without an infrared window, and opening an energized panel exposes personnel to electrical and arc hazards.
Opening and inspecting energized panels must be done only by qualified persons, with the protective equipment and procedures required by applicable regulations.