Principle
Insulation in good condition behaves almost linearly: if the voltage doubles, the current doubles and the calculated resistance does not change. Insulation with cracks, localized moisture, contamination or weak spots can behave non-linearly: it looks fine at low voltages, but as the voltage increases the current grows more than proportionally and the resistance decreases. The step test aims to reveal that non-linearity using voltages higher than those of a conventional spot test.
General procedure
- De-energize, isolate and ground the test object, and discharge any stored energy before connecting.
- Choose the maximum level according to the type of equipment and the recommendations of the manufacturer and the applicable standard, without exceeding what the insulation can withstand.
- Divide that range into equal steps and hold each one for the same time, normally a short, fixed duration.
- Record the current or the resistance at the end of each step.
- When finished, discharge the insulation through a controlled path for an adequate time, since it can retain a dangerous charge.
What an engineer sees in practice
Resistance is plotted against applied voltage. An almost horizontal line indicates homogeneous insulation. A sustained downward slope indicates sensitivity to voltage. A sharp drop at one step points to a weak spot close to puncture and means the test must be stopped. Because absorption effects dominate the first moments, holding each step for the same time is essential for comparison.
How to interpret the result
- A small variation between steps, within the repeatability of the instrument, is usually normal.
- A progressive decrease suggests moisture, contamination or deterioration.
- The insulation temperature must be recorded, because resistance depends on it.
- Results are compared with previous tests on the same equipment and with the other windings or phases.
When it does not apply
The test subjects the insulation to greater stress than a low-voltage measurement; it is not recommended on insulation already known to be badly deteriorated or on equipment with low test limits.
Safety
These voltages can cause serious injury. The test must be performed by qualified personnel, with a lockout/tagout procedure and in accordance with applicable regulations.