This is the classic method for measuring the resistance of an electrode or a grounding system. It is based on a circuit of four elements: the electrode under test, an auxiliary current electrode placed far away, a potential probe that moves between the two, and the instrument that injects alternating current and measures the resulting voltage.
Principle
The current that leaves the electrode under test and returns through the auxiliary electrode creates a potential distribution in the soil. Near the electrode the voltage rises quickly; in an intermediate region it is almost constant; near the auxiliary electrode it rises again. The resistance is obtained as the ratio of the voltage measured by the probe to the injected current, in the zone where the influences of the two electrodes cancel out.
General procedure
- Disconnect the electrode from the system, if this can be done safely, or use a method that tolerates the connection.
- Place the auxiliary current electrode at a distance sufficiently large relative to the size of the electrode.
- Set the potential probe in line and measure at several intermediate positions.
- Plot resistance against probe position.
How to interpret the curve
If the soil is reasonably uniform, the curve shows a plateau. The plateau value is the resistance. In a simplified layout the probe is placed at a fraction close to six tenths of the distance to the auxiliary electrode, a location that gives the correct value in homogeneous soil with small electrodes; with large electrodes that rule is not enough and the complete curve is required.
If there is no plateau, the zones of influence are overlapping: the auxiliary electrode is too close, or there are pipes or other buried metals distorting the field.
Errors and precautions
- Test leads running parallel and close to energized lines, which induce voltages.
- Probes with poor contact because of dry or stony soil.
- Measuring near buried metal structures.
Repeating the measurement with the line in another direction confirms that the value is robust. If voltages could appear because of a fault on the system, the measurement must be performed by qualified personnel, in accordance with the applicable safety regulations.