The resistance of a transmission tower is measured with the fall-of-potential technique adapted to the tower's geometry, and it must be isolated from the effect of the shield wires, which place other towers in parallel.

Each tower on a transmission line has its own grounding, with electrodes, counterpoises or the foundation itself. Its resistance matters because it determines how high the overvoltage is when lightning strikes the tower or the shield wire, and with it the probability of backflashover across the insulators.

The shield wire problem

Towers are usually joined by overhead shield wires. These wires connect the tower under test with all the others, which end up in parallel. If the measurement is made with the shield wire connected, the instrument sees a value much lower than that of the tower alone, because it includes the contribution of the neighboring towers. There are two options for evaluating the individual tower.

Measurement options

  • Disconnect the shield wire from the tower: this allows the isolated tower to be measured by fall of potential. It can only be done with the line out of service and with working grounds applied, by specialized personnel.
  • Selective clamp method: with the auxiliary probes laid out as for fall of potential, a clamp measures the current entering through each leg or through the counterpoise, without disconnecting anything. Measurements on each leg give the value for the tower.

Practical considerations

The auxiliary electrodes require long distances relative to the extent of the tower’s grounding, and the test leads must not run parallel and close to the line conductors, because voltages are induced. On lines near other energized lines, these induced voltages can be dangerous for the person measuring.

How to interpret the result

A high value on an isolated tower makes it more prone to lightning faults, especially on resistive ground. The correction is usually to add counterpoises or electrodes. A tower with very different values between its legs may indicate a damaged connection, often due to conductor theft or corrosion. The acceptance criterion depends on the design of the line.

This activity is carried out near high-voltage lines, so it must only be performed by qualified personnel, following the applicable safety regulations.