In design, touch voltage is calculated. In a finished installation, it can be verified experimentally, because the actual soil, connections and structures differ from the model.
Measurement principle
It is not possible to cause a real fault in order to measure it, so one is simulated. A test current, much smaller than the fault current but still measurable, is injected into the ground grid using a remote return. This current sets up a potential field in the soil. The voltage is measured between an accessible metal structure and a reference electrode placed on the surface at the spot where a person would stand.
How the feet and body are simulated
The reference on the ground is made with plates or weights that represent the contact area of the feet. The voltmeter is connected with a series resistance that represents the body impedance, so that the reading corresponds to the voltage a person would actually receive, and not to the open-circuit voltage, which would be higher.
From test value to fault value
Since the behavior is approximately linear, the voltage measured with the test current is multiplied by the ratio of the expected fault current to the injected current. That scaling must use the portion of the current that is actually dissipated into the soil. The scaled value is compared with the tolerable limit set by the standard in force.
Limitations
- The test current must be high enough for the reading to stand out from the noise of stray currents in the network.
- The result depends on the moisture and the surface layer on the day of the measurement.
- Measurements are made at selected points, not at all of them; it is advisable to choose those with the highest risk, such as structures on the perimeter.
How to interpret the result
A reading above the limit indicates a point where it is advisable to check the continuity between the structure and the grid, the conductor spacing or the surface layer. These tests are carried out in installations with electrical hazards. They must be performed only by qualified personnel, following the applicable safety regulations.