How Is the Breakdown Voltage of an Insulator Measured?

The breakdown voltage of an insulator is determined by raising the test voltage until a disruptive discharge occurs, repeating the test and applying corrections for atmospheric conditions.

What breakdown means in an insulator

In an outdoor insulator, the disruptive discharge is almost always an external arc, or flashover, that travels through the air and along the surface; in a solid insulator it sometimes punctures the material. Both cases end in a short circuit, but their causes and their significance are different.

How it is done

  1. The insulator is mounted as in service, with defined hardware and clearances to grounded objects, because these influence the result.
  2. The type of voltage is selected: power-frequency, DC or impulse, according to the application of the insulator.
  3. The voltage is raised gradually, or impulses of increasing amplitude are applied, until the discharge occurs.
  4. The voltage at the instant of discharge is recorded with a measuring system using a voltage divider and a peak voltmeter or digitizer.
  5. The test is repeated several times. Because discharge is a statistical phenomenon, a single value is not representative; the work is done with mean values and scatter.

Why conditions matter

  • Atmosphere: air density, humidity and temperature alter the flashover voltage, so they are recorded and the result is corrected to reference conditions.
  • Surface condition: dry, under artificial rain or artificially contaminated. The results are very different in each condition.
  • Waveform: a fast impulse and a sustained voltage can give different values.

How to interpret the result

The measured value is compared with the withstand voltage specified for that insulator. A breakdown test and a withstand test are different things: the former seeks the limit and is usually destructive to the material if it punctures; the latter verifies that a level is reached without discharge.

These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.