What breakdown means in an insulator
In an outdoor insulator, the disruptive discharge is almost always an external arc, or flashover, that travels through the air and along the surface; in a solid insulator it sometimes punctures the material. Both cases end in a short circuit, but their causes and their significance are different.
How it is done
- The insulator is mounted as in service, with defined hardware and clearances to grounded objects, because these influence the result.
- The type of voltage is selected: power-frequency, DC or impulse, according to the application of the insulator.
- The voltage is raised gradually, or impulses of increasing amplitude are applied, until the discharge occurs.
- The voltage at the instant of discharge is recorded with a measuring system using a voltage divider and a peak voltmeter or digitizer.
- The test is repeated several times. Because discharge is a statistical phenomenon, a single value is not representative; the work is done with mean values and scatter.
Why conditions matter
- Atmosphere: air density, humidity and temperature alter the flashover voltage, so they are recorded and the result is corrected to reference conditions.
- Surface condition: dry, under artificial rain or artificially contaminated. The results are very different in each condition.
- Waveform: a fast impulse and a sustained voltage can give different values.
How to interpret the result
The measured value is compared with the withstand voltage specified for that insulator. A breakdown test and a withstand test are different things: the former seeks the limit and is usually destructive to the material if it punctures; the latter verifies that a level is reached without discharge.
These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.