How is temperature measured through an infrared window?

To measure through an infrared window, use an infrared-transparent material, tell the camera the window transmittance, and pay attention to its cleanliness, angle and temperature.

Why ordinary glass does not work

Ordinary glass lets visible light through but blocks the thermal infrared in which common cameras work: it acts as both a mirror and a screen. An inspection window uses materials that do transmit that band, such as certain crystals or polymers.

A transmittance below one

Even a suitable material lets through only a fraction of the radiation, and reflects and absorbs the rest. If the camera does not know this, it will interpret the reduced signal as a lower temperature. That is why the measurement requires correction.

How it is corrected

  1. Obtain the window transmittance in the camera’s band from the window manufacturer’s data.
  2. Enter that figure in the camera parameter for external optics or windows, along with the window temperature.
  3. Keep the correct emissivity setting for the object.
  4. If the manufacturer’s data is not reliable, estimate the effect by comparing a reading with and without the window on the same stable target, when this can be done safely.

Measurement precautions

  • Look perpendicular to the window; at oblique angles reflection increases and transmittance falls.
  • Keep the window clean; dust and fingerprints reduce the signal.
  • Avoid reflections from heat sources striking the window.
  • Bear in mind that the window itself also emits if its temperature changes.
  • Confirm that the field of view allows the component to be seen through the window diameter.

What an engineer sees in practice

Consistently low readings at all points viewed through the window, when compared with an open window or a historical measurement. This indicates uncorrected transmittance.

Opening the equipment or any work near energized parts must be done by qualified personnel in accordance with applicable regulations.