Why thermography
A loose or deteriorated connection has higher resistance, and the power dissipated in it grows with the square of the current. This heats it up before it fails. An infrared camera makes these hot spots visible from a distance, without contact and during operation, because it detects the infrared radiation emitted by the surface.
General procedure
- Measure under load. Heating depends on current, and a lightly loaded panel can hide a defect. The current of each circuit is recorded at the time of the image.
- Set the camera emissivity to the material and finish of the surface. Shiny metals emit little and reflect a lot, which produces misleading readings.
- Observe from a suitable angle, avoiding reflections from nearby heat sources.
- Capture images of each phase of the same device and of similar devices under similar load.
- Document the image, location, current, ambient conditions and emissivity used.
How to interpret
The difference between similar phases carrying the same current, or against a reference point in good condition, is more informative than the absolute temperature. A spot significantly hotter than its equivalents indicates a probable problem. The criteria for classifying urgency come from standards and the manufacturer, and must be consulted in their current edition. If the current was low during the inspection, the real problem may be greater than what was seen.
Alternatives and complements
- Contact thermometers or fixed sensors, especially on critical busbars, with continuous monitoring.
- Infrared windows that allow inspection without removing covers.
- Records of ambient temperature and enclosure ventilation.
Common mistakes
- Measuring with the panel almost unloaded.
- Leaving the emissivity at its default on metal surfaces.
- Measuring through glass or polycarbonate, which do not transmit infrared well.
- Interpreting by absolute temperature without comparing.
Opening energized panels involves an arc flash hazard; it must be done by qualified personnel with the protective equipment and procedures required by applicable regulations.