What surface leakage current is
Dust, salt and contaminants build up on the surface of an insulator. With moisture, they form a conductive film through which a small current flows. That current causes heating, dry bands with arcing and, if left unchecked, a complete flashover. Measuring it shows how much active contamination the insulator carries.
Two ways to measure it
With the insulator out of service
The test voltage is applied and the meter is connected so that only the current of the path of interest passes through it. The guard terminal diverts the current of the other path to ground, bypassing the meter. If the guard surrounds the measurement area on the surface, the instrument records the volume current; if the meter is placed in the surface path and the volume is guarded, it records the surface current. The result depends on how the measuring electrode and the guard are connected, which is why the setup must be clearly defined.
In service
A sensor is installed on the ground connection of the structure or at the base of the insulator and the current is recorded continuously. The signal contains a capacitive component, which does not indicate deterioration, and a resistive component, which does. For this reason its harmonic content or its component in phase with the voltage is analyzed: an increase in harmonics, particularly the third, points to non-linear behavior caused by surface activity.
Influencing factors
- Humidity, fog and condensation: they wet the contamination and increase the current markedly.
- Type and amount of contaminant: sea salt and industrial deposits conduct more than dry dust.
- Insulator profile and material: hydrophobic materials limit the formation of continuous films.
- Temperature and ventilation.
How to interpret the result
The evolution of the current over time and its correlation with the weather are observed. Peaks that coincide with fog or light rain are common; growing peaks that persist in dry weather, or intermittent activity, indicate contamination and a risk of flashover. Thresholds are set according to the experience at each site, and cleaning or coating is scheduled before the critical season.
Safety
These measurements are made in high-voltage installations. They must be performed by qualified persons, observing safety clearances and grounding and following applicable regulations.