The protective conductor exists to give fault current a low-impedance path back to the source. If that path is interrupted or has high resistance, the protection may not trip and the enclosure remains energized. The continuity test confirms that the path exists and has low resistance.
What is measured
The resistance is measured between the main grounding terminal of the installation, or the point where the conductor originates, and each remote point: enclosures, ground terminals of receptacles, connected metal structures and bonding jumpers.
Instrument and connection
A low-resistance ohmmeter is used, which injects a DC or AC test current and measures the voltage drop. The higher the test current, the less influence is exerted by oxidized or thin contacts that could mask a defective connection. Before measuring, the resistance of the test leads is compensated, either by subtracting it or with the instrument’s zeroing function, because it could be comparable to the value being measured.
How it is done
- Verify that the circuit is de-energized and locked out according to procedure.
- Connect one end to the main grounding terminal and the other to the point being checked.
- Take the reading, then reverse the test polarity to confirm that the reading is stable.
- Move the conductor at the connection point; a fluctuating reading indicates a loose contact.
How to interpret the result
The resistance depends on the length and cross-section of the conductor, so it is compared with the value expected for that run. A reading much higher than the value calculated for the conductor indicates a defective connection. A reading that changes when the leads are moved points to a poor contact. In certain schemes, the continuity test is complemented by measuring the fault loop impedance, which includes the source.
What to check first
The connection points are checked: loose screws, paint under terminals and severed conductors. The tests must be done with the circuit de-energized. Verifying electrical installations is work for qualified personnel, in accordance with the applicable safety regulations.