24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

How is the temperature of an overhead line measured from the ground?

From the ground, an overhead line is measured with a telephoto-equipped camera, concentrating on connections and splices, and taking into account distance, wind, sun, conductor emissivity and viewing angle.

A case of adverse measurement

The line combines several difficult factors: the target is thin, far away, viewed against the sky, has a low-emissivity metal surface and is exposed to wind and sun.

Problems and how they are addressed

  • Target size: a conductor occupies few pixels at a distance, and the reading is averaged with the colder sky. Lenses with a longer focal length are used, and a closer observation point is sought.
  • Low emissivity: clean metal cable reflects the surroundings and the sun. Splices, connectors and oxidized or dirty areas have better emissivity and are the points where thermography is most useful.
  • Wind: it cools the conductor and can conceal heating. Its speed is recorded, and measuring in light wind is preferred.
  • Sun and reflections: solar heating and direct reflection confuse the image; it is advisable to measure under overcast skies or with no incident sun, and from an angle that avoids the reflection.
  • Atmosphere: the long distance makes air humidity and temperature relevant, and they must be entered in the camera.
  • Angle: viewing at a very steep angle reduces the effective emissivity.
  • Load: the current determines the heating and must be obtained from the line operator.

What can be concluded

From the ground, differences between similar elements are readily detected, such as a connection much hotter than the adjacent ones. The absolute temperature of the conductor is difficult to obtain accurately. Comparison between spans or phases under similar conditions is more reliable than the isolated value.

When another technique is advisable

To quantify with greater certainty, close-up inspection from platforms or with aerial vehicles makes it possible to get near without touching the conductor.

Work near energized lines involves safety distances and must be carried out by qualified personnel following applicable regulations.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer