24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

How Is the Insulation Resistance of a Medium-Voltage Cable Measured?

The insulation resistance of a medium-voltage cable is measured between each conductor and its grounded shield, with the cable de-energized and isolated at both ends.

What is measured

The test evaluates the insulation between the conductor and the metallic shield, which is grounded. This measurement reveals moisture, contamination at terminations or serious damage, but it does not detect incipient localized defects, such as voids or trees, which call for other diagnostics.

Essential steps

  1. De-energize, isolate and ground both ends of the cable, verifying the absence of voltage and discharging it. A long cable stores considerable charge.
  2. Disconnect the cable from transformers, switchboards or surge arresters at both ends and keep the terminations separated.
  3. Measure each phase with the other two and the shield grounded. In this way each conductor is tested against everything else.
  4. Apply the guard at the terminations if there is surface leakage due to dirt or moisture.
  5. Record readings at defined times, together with the cable and ambient temperatures.

The effect of length

All the insulation along the cable acts like resistances in parallel. As a result, total resistance decreases as length increases, and a short cable and a long cable of identical quality give different values. To compare cables, values are normalized by length according to the criterion adopted. In addition, a long cable has high capacitance: the charging current takes longer to decay and the reading stabilizes more slowly.

How to interpret the result

Very low values, or values that differ between phases, point to a problem. Acceptable values do not guarantee that the cable will withstand the service voltage; withstand or diagnostic tests are used to confirm this. New cables are compared with the acceptance specification, and existing cables with their history.

When it does not apply

On its own, this test cannot evaluate a cable suspected of electrical treeing or water treeing in the extruded insulation.

These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer