24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

How is the resistance of an electrode measured without disconnecting it?

The resistance of an electrode can be measured without disconnecting it using methods that separate the electrode's current from the rest of the system, such as selective clamp measurement, or with a clamp that measures a closed loop.

Disconnecting an electrode to measure it is not always possible or safe: it can leave equipment unprotected. That is why methods exist for measuring it while connected. There are two families that should not be confused.

Selective measurement

This is a variant of fall of potential. The auxiliary probes are placed as in the classic method, but the current actually flowing through the electrode under test is measured with a clamp around its down conductor only. The calculated resistance thus corresponds solely to that electrode, even though it is connected to the system and to other electrodes in parallel. It requires driven probes, but it avoids opening connections.

Loop clamp measurement

The clamp has two cores: one induces a known voltage in the loop and the other measures the resulting current. The ratio is the total resistance of the loop. This method needs no probes, but it requires a closed loop, that is, other return paths to ground, such as many electrodes connected to a common neutral.

What each one measures

  • Selective measurement gives the resistance of the individual electrode.
  • The loop clamp gives the resistance of the electrode plus that of the rest of the loop. If the rest has a very low resistance, the value approaches that of the electrode; if not, it reads above it.

When it does not apply

The loop clamp does not work on a single, isolated electrode with no other return path: there is no loop and the instrument cannot measure. Nor is it reliable if the loop includes loose connections that change its value, or if there are significant leakage currents in the conductor. Interference from stray currents can affect both methods.

How to interpret the result

A low loop value does not prove that the individual electrode is in good condition; it only indicates that the complete loop has low resistance. To evaluate a particular electrode, the selective method or measurement with controlled disconnection is preferable. Work on energized ground conductors must be performed by qualified personnel, in accordance with safety regulations.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer