Measuring the current in a ground conductor shows whether current that should not be there is flowing through it. In a healthy protective conductor, the current during normal operation is small; an appreciable current indicates leakage, neutrals connected to ground at more than one point, or return currents following unintended paths.
How it is measured
A clamp meter is placed around the conductor, without interrupting the circuit. The clamp detects the magnetic field produced by the current. Only the ground conductor should be clamped, not a cable that also contains phases or neutral, because opposing currents would cancel out in the reading.
Choosing the instrument
- Sensitivity: leakage currents are small, so a clamp with good resolution on low ranges is required. A general-purpose clamp may read zero when current is actually present.
- True RMS: electronic loads produce non-sinusoidal currents. An instrument that assumes a sine wave can give significant errors.
- Bandwidth: if harmonics are of interest, the instrument must cover them.
What is interpreted
The ground current is compared with what is expected. If current flows in a protective conductor during normal operation, the causes are investigated: insulation leakage in loads, interference filters that divert current to ground, or a neutral bonded to ground downstream of the authorized point. In a three-phase system with electronic loads, zero-sequence harmonic current adds up in the neutral and can appear in the ground paths if there are improper bonds.
An example reading
If the current in the ground conductor of a panel changes when a downstream breaker is opened, that load is the source of the leakage. This way of "sectioning" the installation makes it possible to locate the origin by elimination.
Precautions
A ground conductor is never disconnected while the circuit is energized. The clamp must be suitable for the measurement category of the location, and bringing it close to conductors in energized enclosures must be done by qualified personnel, following the applicable safety regulations.