What is measured and why
Ideal insulation behaves like a perfect capacitor: the current leads the voltage by 90 degrees. In real insulation, part of the current is in phase with the voltage because of dielectric losses. The tangent of the loss angle, or dissipation factor, is the ratio of the loss current to the capacitive current. Insulation that is wet, aged or degraded has higher losses.
How the measurement is made
- With the cable de-energized, isolated and grounded at both ends, accessories that are not part of the test are disconnected.
- The AC voltage source is connected to the conductor and the measurement is taken from the shield. Digital instruments determine the phase angle between voltage and current; classic bridges seek a balance.
- Voltage is applied in steps, from a low value to near the service voltage, and capacitance and dissipation factor are recorded at each step.
- The cable is discharged and grounded before the connections are handled.
The measurement can be made at power frequency or at very low frequency, depending on the equipment available.
What to expect from each quantity
- Capacitance: depends on the geometry and permittivity of the insulation, and is proportional to length. Significant changes from the expected value, or differences between phases, are abnormal.
- Dissipation factor: in a healthy cable it is low and nearly constant with voltage. An increase as voltage rises, the so-called tip-up effect, indicates degradation such as moisture or treeing.
How to interpret the result
There is no universal rejection value: results are compared with similar cables, with the other phases and with previous measurements, corrected for temperature. A cable with a rising trend in losses warrants complementary diagnosis with partial discharge testing.
Dirty or wet terminations can distort the measurement, so they must be clean and dry.
These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.