How Do You Interpret the Insulation Resistance Trend Over Time?

The insulation resistance trend is interpreted by comparing readings from the same equipment, taken under equivalent conditions and corrected for temperature; the direction and speed of the change matter more than an isolated value.

Why an isolated reading says little

Insulation resistance depends on the type of insulation, its size, the temperature and the humidity. The same value can be normal on one piece of equipment and worrying on another. By contrast, the history of a single piece of equipment always measured the same way is very informative: it shows how the insulation ages, becomes contaminated or takes on moisture.

Conditions for comparison

  • Same test voltage and same application time.
  • Same connections and same equipment state (disconnected from the same circuits).
  • Values brought to a common reference temperature.
  • Consistent instrument and method.

If any of these conditions changes, the observed difference may come from the method and not from the insulation.

How to read the graph

Plotting corrected resistance against date makes it possible to distinguish different behaviors:

  • Gradual, sustained decline: this is to be expected from aging, but a slope that steepens warrants investigation.
  • Sudden drop between two measurements: this suggests an event: water ingress, heavy contamination, mechanical damage or overheating.
  • Values that recover after cleaning or drying: these indicate that the problem was on the surface or due to moisture.
  • Scatter with no pattern: this usually reveals inconsistent measurements rather than a real problem.

How to interpret the result

A downward trend does not in itself require taking equipment out of service, but it indicates that the interval between tests should be shortened and that other measurements should be added, such as the polarization index or the dissipation factor. The final decision combines the trend with the manufacturer’s criteria, the criticality of the equipment and the applicable standard.

In addition to the resistance reading, always record the temperature and ambient humidity of each test, because these are the variables that most often explain an apparent change.

These activities involve hazardous voltages: they must be performed by qualified, authorized personnel, following applicable regulations and the facility’s lockout and grounding procedures.