How is an apparent soil resistivity curve interpreted?

An apparent resistivity curve shows how the measured resistivity changes as the electrode spacing increases; its shape indicates whether the ground becomes more or less resistive with depth, but the apparent value is not the true resistivity of any layer.

How it is obtained

In the Wenner method, four equally spaced electrodes are driven in a line. Current is injected through the outer electrodes and the voltage is measured between the inner ones. Apparent resistivity is calculated from the measured resistance and the spacing. When this is repeated with increasing spacings, the current penetrates deeper and the measurement is influenced by progressively deeper layers. The plot of apparent resistivity against spacing is the curve.

What the shape indicates

  • Rising curve: the deep layers are more resistive than the surface layers (for example, rock under moist soil).
  • Falling curve: the ground becomes more conductive with depth (for example, the water table or a clay stratum).
  • Nearly flat curve: approximately uniform soil.
  • With maxima or minima: several layers with different contrasts.

Apparent is not true

Apparent resistivity is what a uniform soil giving the same reading would have. In stratified ground, the reading blends the contribution of several layers. To obtain resistivities and thicknesses for each layer, a model, commonly of two or more horizontal layers, is fitted to the measured curve, using manual methods or inversion software. The spacing is not an exact measure of the depth investigated, only a guide.

How to interpret the result

  1. Check that the points are continuous; abrupt jumps usually indicate measurement errors, nearby buried metal or poor electrode contact.
  2. Measure in several directions and locations, because the ground is not laterally homogeneous.
  3. Fit the layer model and validate that it reproduces the curve without physically absurd parameters.
  4. Use the model in the design of the grounding grid; the sensitivity of the design to the surface layer is usually high.

What the engineer sees in practice

The field curve with separate points, sometimes scattered, and a fitted model overlaid. The surface layer, the one most affected by moisture and temperature, can vary with the seasons, so the measurement date is relevant information.

Warning: grounding systems protect against electrical hazards. Their study, design and measurement must be carried out by qualified personnel, in accordance with the applicable regulations.