How is a high-resistance ground improved?

A high-resistance ground is improved by increasing contact with the soil: more well-spaced parallel electrodes, greater depth or extension, or treatment of the surrounding soil, after verifying the cause.

The resistance of an electrode depends on soil resistivity and on its geometry. Reducing it means acting on one of those two factors: giving the electrode more contact area with the soil or reaching soil that conducts better.

First, understand the cause

Before adding material, it is advisable to measure resistivity by layers. If the surface layer is dry and resistive and there is a more conductive layer below, the solution is to go deeper. If the soil is resistive throughout the profile, it is better to extend the system or enlarge the area. Simple causes must also be ruled out: loose connections, corroded joints or a damaged electrode.

Common options

  • Parallel electrodes: the resulting resistance falls, but only if they are far enough apart that their zones of influence do not overlap. Rods placed very close together behave almost like a single rod.
  • Greater depth: useful when the deep layers are damper or less resistive, and less sensitive to seasonal variation.
  • Horizontal conductors or counterpoises: they increase the dissipation area in soils where it is not possible to go deeper.
  • Ground enhancement backfills: materials that reduce the local resistance between the electrode and the soil.
  • Connection to other buried structures: such as foundations, which already provide contact with the soil, when the standard allows it.

How to decide

The choice depends on the resistivity profile, the available space and the maintenance that is possible. Chemical treatments can lose effectiveness over time and can be aggressive toward the environment and the metal, so their permanence and compatibility must be evaluated.

How to verify the improvement

Measure before and after with the same method and, preferably, under comparable moisture conditions. A change that works only in the rainy season does not solve the underlying problem. The acceptance criterion depends on the application and the current standard. Work on the grounding systems of energized installations is the responsibility of qualified personnel.