How is a tank or metal structure grounded?

It is connected with bonding conductors to the ground grid to drain static charges and divert lightning and fault currents, ensuring continuity between all metal parts and compatibility with cathodic protection if present.

Why it is grounded

A tank or metal structure can accumulate electrostatic charge, receive a lightning strike or become energized by a fault in nearby equipment. Grounding means giving that charge or current a low-impedance path to the soil and keeping all parts at the same potential.

Connection principles

  • Continuity. Parts joined with seals, flanges or gaskets may not be conductive. Bonding jumpers are installed to ensure electrical continuity between sections.
  • Connection points. Several are used, distributed over the structure, so that the failure of one connection does not leave the assembly isolated.
  • Durable connection. With connectors suited to the material and to the weather, accessible for inspection.
  • Electrode. The structure is bonded to an electrode or to the site grid. For static, the requirement is mainly continuity and a moderate resistance, while for lightning what matters is that the system dissipates high-frequency currents through short, multiple paths.

Cases with flammable fluids

When a flammable liquid is transferred between a truck and a tank, both must be electrically bonded to each other and to ground before the transfer begins, so that there is no potential difference that could cause a spark in the presence of vapors. Hoses and connections must also maintain continuity.

When the general rule does not apply

If the tank has cathodic protection, connecting it directly to a copper grid can consume the protection current and accelerate corrosion. In these cases specific designs are used, for example with isolation devices that block direct current and let fault and lightning currents through. This is defined by whoever designs the cathodic protection system.

How it is verified

Continuity measurement between the parts and the connection point, visual inspection of the joints, and measurement of the resistance of the electrode or system to which it is connected. This is repeated periodically because corrosion and maintenance work alter the joints.

In areas classified for flammable or explosive atmospheres, the work must be done by qualified personnel in accordance with the applicable regulations. Measurements and work in energized electrical installations must be done by qualified personnel, following the applicable regulations and the site’s safety procedures.