Two distinct functions
In a photovoltaic system, equipment grounding, which is a safety function, must be distinguished from system grounding, which sets a reference for one of the live conductors. They are different decisions and both do not always apply.
Equipment grounding
Module frames, support structures, junction boxes and inverter enclosures are connected to each other with a grounding conductor. The purpose is that, if a live conductor touches a metal part, there is a low-impedance path so that enough current flows for the protection to operate, and that no potential differences exist between exposed metal parts.
- Anodized aluminum frames require connectors designed to pierce or penetrate the oxide layer and ensure metal-to-metal contact.
- Care is taken with metal compatibility in joints exposed to the weather, to avoid galvanic corrosion.
- The structure is bonded to the site grounding system, so that everything shares the same reference.
DC side
Depending on the design, the array can operate with one pole connected to ground or isolated from ground. An isolated system uses an insulation monitor that detects leakage to ground; a system with a grounded pole uses ground-fault protection. Transformerless and galvanically isolated inverters behave differently, and the manufacturer defines which configuration is permissible.
AC side
The inverter connects to the site network with its own grounding conductor, and the bond between neutral and ground is kept where it belongs in the system, normally at a single point.
Lightning and overvoltages
A large array on a rooftop or in open country is vulnerable. Surge protection is used on the DC and AC sides, and careful equipotential bonding is maintained to limit induced voltages. Large loops formed by string cables increase induced voltages, so it is advisable to run the outgoing and return wiring together.
What to check first
Continuity between frames and structure, the condition of joints, electrode resistance and the grounding configuration the inverter requires. Measurements and work in energized electrical installations must be done by qualified personnel, following the applicable regulations and the site’s safety procedures. A photovoltaic array produces voltage whenever there is light, even with the system disconnected from the grid.