A flooded generator is evaluated without energizing it: the damage is documented, the machine is cleaned and dried in a controlled way, and insulation resistance is monitored until it can be decided whether to return it to service, rewind it or replace it.

First rule: do not energize

A generator that has been in contact with water has contaminated, damp insulation. Energizing it or turning it to test it can cause a short circuit that destroys the winding and damages the machine. Evaluate first.

What makes a flood different

Water carries mud, salts and contaminants that remain in the windings and ventilation ducts. If the water is salty or contains chemical residues, the damage is worse, because the deposits keep conducting and corroding even after drying. Other affected items are bearings, lubricant, space heaters, brushes and slip rings, the exciter, control boards and wiring.

Work sequence

  1. Document the height the water reached and the condition of the machine, with photographs and notes, to support the decision and, if applicable, a claim.
  2. Disconnect and protect the machine from any energy source.
  3. Remove the mud and clean with methods suited to the type of insulation, avoiding jets that would introduce more water.
  4. Dry in a controlled way with moderate heat and air circulation, without raising the temperature abruptly, because trapped moisture could produce steam and damage the insulation.
  5. Measure the insulation periodically during drying. Resistance rises as moisture is removed and stabilizes when drying is complete.
  6. Check bearings, lubricants and mechanical components, which are usually replaced.
  7. Test the auxiliary and control circuits before attempting a start.

How to interpret the result

If the insulation does not recover satisfactory values after cleaning and drying, or if the deposits are corrosive, the option is to rewind or replace. The decision is based on the trend of the measurements and on the manufacturer’s instructions.

These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.