Why it is documented
A thermography report must allow someone who was not on site to understand what was measured, under what conditions and why a conclusion was reached. It also serves for comparison with future inspections and for detecting trends.
Data worth recording
- Identification: equipment, location, date and time, and person who performed the inspection.
- Operating conditions: load or current in each phase at the time of the shot, and operating mode.
- Ambient conditions: ambient temperature, humidity, wind, presence of sun or reflective sources.
- Camera and optics: model, serial number and status of its verification or calibration.
- Measurement parameters: emissivity, reflected apparent temperature, distance, atmospheric humidity and temperature, and how the emissivity was obtained.
- Images: one thermal and one visible image of the same scene, with a legible temperature scale and the measurement points marked.
- Reference: which component it was compared with and what temperature that component was at.
Analysis and conclusion
Each finding includes the temperature difference, the probable cause, the severity level and the recommended action. It is advisable to separate what was measured from what is interpreted, and to point out limitations, such as inaccessible components or low load.
Traceability
Keep the original radiometric files, not just the report images: they allow recalculation with other parameters if an error is detected. If any data item was not recorded, state this and do not fill it in with assumptions.
An example of good practice
A finding identified as “center phase connection, feeder 3 breaker” with the load conditions and a visible image can be located again without ambiguity months later. One described as “hot spot in panel” cannot.
The exact structure of the report is usually defined by the applicable procedure or the customer.