Why it matters that it recurs
A single fault may be an isolated event. One that repeats indicates a persistent condition: something in the environment, the load or the configuration is pushing the drive to its limit. Replacing it without understanding the cause usually reproduces the problem.
Start with the history
Drives log the fault code, the time and, on many models, the current, the bus voltage and the frequency at that instant. Note when it occurs: on starting, accelerating, braking, at full load or at certain times of day. The pattern guides almost the entire diagnosis.
Fault families and their typical causes
- Overcurrent: acceleration ramp too short, a jammed mechanical load, a short circuit or insulation failure in the cable or motor, or an incorrectly entered motor parameter.
- DC bus overvoltage: rapid deceleration of a high-inertia load returns energy to the bus. It can also be due to a supply with spikes. It is corrected by lengthening the ramp or with a braking resistor.
- Undervoltage: sags or dips in the supply, loose connections at the input, or an undersized feeder.
- Overtemperature: obstructed ventilation, deteriorated fans, a hot enclosure, or a switching frequency too high for the conditions.
- Ground fault: deterioration of the motor or cable insulation, or moisture.
- Phase imbalance or phase loss: a deficient fuse, contact or connection at the input.
What to check first
- Physical condition: dust, filters, fans, tight connections, discoloration.
- Input voltage and balance between phases, ideally logged over several hours to catch events.
- Motor and cable insulation with the appropriate instrument, with the drive disconnected.
- Motor parameters against the nameplate, and ramps against the load inertia.
- Control wiring and shielding, since noise causes apparently random trips.
When to suspect the drive
If the supply, motor, load and environment have been ruled out, and the same fault appears at light load or with no motor, suspect the power electronics or aged bus capacitors. Work on mains and DC bus voltages must be done by qualified personnel, waiting for the bus to discharge before opening the equipment.