What a mat protects against
An insulating mat places a high-resistance surface between the feet and the floor, and it reduces the current that would pass through the body if an energized part is touched or a fault occurs. It is complementary protection; it does not replace personal protective equipment or other measures.
Inspection before use
- Marking: the class or voltage for which it was manufactured and the manufacturer’s information must be visible. If they can no longer be read, its capacity must not be assumed.
- Surface: look for cuts, punctures, cracks, burns, deep abrasion and embedded metal objects such as swarf or nails.
- Flexibility and texture: the material must not be hardened, brittle or sticky; these changes indicate aging or contact with oils and solvents.
- Edges and corners: if they have lifted, curled or broken, they are points of risk and trip hazards.
- Cleanliness: conductive dirt, moisture or grease residue can create surface leakage paths.
Dielectric tests
Visual checks do not reveal internal faults. To confirm the insulating capacity, the mat undergoes dielectric tests in a specialized laboratory or workshop, with the voltage and procedure defined by the product standard and the manufacturer. The frequency of these tests is set by the standard and by company policy. A field measurement with a megohmmeter can show trends, but it does not replace the formal test.
Conditions of use
- Lay it flat, without folds, covering the entire area where the operator stands.
- Keep it dry and clean, with no cables on top that could damage it.
- Use it at the voltage for which it is rated.
- Avoid prolonged exposure to heat, sunlight and chemicals.
When to remove it
It is removed in the event of any damage that passes through its thickness, contamination that cannot be removed, illegible markings or an expired test. It is not repaired with improvised patches.
Work in areas with electrical risk must be carried out by qualified personnel in accordance with the applicable regulations.