How is the Wenner method applied for resistivity?

The Wenner method measures soil resistivity with four electrodes in line and equally spaced: the outer ones inject current, the inner ones measure voltage, and an apparent resistivity is calculated.

In the Wenner method, four small electrodes are driven in a straight line, with the same spacing between each consecutive pair. An instrument injects alternating current through the two outer electrodes and measures the voltage between the two center ones.

How the result is obtained

The instrument calculates a resistance as the ratio of voltage to current. To convert it into apparent resistivity, a simple relationship is used: apparent resistivity is two pi times the electrode spacing times the measured resistance. This expression is valid when the depth to which the electrodes are driven is small compared with the spacing.

Why it is repeated with different spacings

The spacing roughly defines how deep the measurement "sees". Small spacings explore the surface layer; large spacings also bring in the deeper soil. Repeating the measurement with increasing spacings produces a curve of apparent resistivity against spacing, and its shape shows whether the soil is uniform or made up of layers.

Summary procedure

  1. Define the measurement line and its orientation, avoiding parallel buried pipes.
  2. Place the four electrodes with equal spacing and shallow depth.
  3. Measure the resistance and calculate the apparent resistivity.
  4. Repeat with other spacings and in another direction, perpendicular to the first.

An example of how to read it

If apparent resistivity grows with spacing, the deep soil is more resistive than the surface soil: for example, a damp layer over rock. If it decreases, the deep soil conducts better, as happens when a water table is reached. If two perpendicular directions give very different values, there is lateral heterogeneity or the effect of buried metal.

Precautions

Results are affected by recent moisture, metal pipes, fences and buried cables. Record the soil condition and the measurement date. When the soil is not uniform, the value from a single spacing must not be used as if it were the resistivity of the site. On sites with buried or nearby energized installations, the measurement must be performed by qualified personnel.