What problem it solves
The current measured by a megohmmeter has several paths: through the volume of the insulation, which is what matters, and along the surface, which is affected by dust, moisture or salt. If both pass through the measuring circuit, the resistance reading drops and there is no way to tell whether the insulation is damaged or merely dirty.
How the guard terminal works
The guard terminal is at the same potential as the line terminal, but outside the measuring circuit. Any current reaching it returns to the source without passing through the meter. When the guard is connected to the surface path, that leakage is diverted and the reading reflects only the volume insulation.
Connection examples
- Cable termination: a few turns of bare wire are wrapped around the insulation near the termination and connected to the guard. The leakage running over the surface between the conductor and the shield is diverted.
- Bushing or wall bushing: a conductive ring is placed on the porcelain and connected to the guard.
- Measuring insulation between two points of a system with several parts: the guard is connected to the part that is not to be measured but would create a parallel leakage path.
How to interpret the result
If the reading rises noticeably when the guard is connected, surface leakage was significant and the volume insulation is in better condition than it appeared; the surface should be cleaned. If the reading does not change, the leakage comes from the volume of the insulation and the guard adds nothing.
When it does not apply
With very clean, dry insulation, or when there is no identifiable surface path, the guard is unnecessary. An incorrect connection can also falsify the measurement, so the guard must be connected deliberately to the surface and not to ground.
These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.