What you are looking for
A photovoltaic module converts part of the light into electricity and the rest into heat. If a cell or a contact is malfunctioning, dissipation concentrates and an area hotter than its neighbors appears. Thermography makes it possible to see that pattern without interrupting generation.
Typical patterns
- Hot spot in a cell: a damaged, cracked, or partially shaded cell, which dissipates instead of generating.
- A hotter strip or section of the module: possible activation of a bypass diode.
- An entire module hotter than the rest: may indicate that it is not delivering current to the circuit.
- Hot junction box or connectors: contacts with high resistance.
- An entire string that looks different: a wiring, protection, or tracking problem.
Measurement conditions
The thermal pattern is clear only with sufficient irradiance on the plane of the modules and stable conditions, because the current flowing depends on the light. Passing clouds must be avoided. Wind cools the modules and reduces contrast.
The reflection problem
The glass cover reflects the sky, which looks cold in the infrared, as well as the sun and nearby objects. Perpendicular viewing can return the camera’s own image. That is why viewing is done at an oblique angle, without going to extremes that increase reflection, and modules are always compared with neighboring ones taken from the same angle. Many inspections are done from drones, with the same angle criterion.
How to interpret
- The measured temperature is that of the glass or the back face, not of the cell.
- The difference from equivalent modules is reported, not just an absolute value.
- Each finding is located by its position in the array.
A photovoltaic array produces DC voltage as long as there is light, and it cannot be “switched off.” Work on the circuits is done by qualified personnel in accordance with applicable regulations.